Recent Articles
Flow-X Prover Detector switch configuration
The Flow-X requires a logical state transition—specifically, from 0 to 1—to start and stop counting during a proving run. This transition is based on logical state, not raw input voltage. If the prover’s detector output is normally 24VDC and drops to ...
FlowX Web Service example commands
In the examples, I am using 10.1.10.200 as the IP. <ip>/archives - will display all of the archives along with the tags that are configured in each, it will not provide the values, just the definition. <ip>/snapshots?filter&ascending=0 - will send ...
FlowX - Using Debug Logs Online to View Incoming Web Requests
How to use online tools to troubleshoot issues. Please view the attachment to see instructions on how to.
How to simulate proving using a FlowX flow computer
How to simulate proving with the Flow-X flow computer This How to instruction will provide an example of how to program the FlowX to simulate proving a meter. Most newer flow computers require live pulses and detector inputs to prove a meter. Wiring ...
IO Calibration
Calibration Calibration can be done on two levels 1. I/O calibration Calibration of analog inputs, PT-100 inputs and analog outputs 2. Calibration of process inputs Loop calibration of any process input (temperature, pressure, density, viscosity, ...