Wiring Hart input to Flow-x
The first 4 analog input circuits of each Flow-X/M flow module have an on-board HART modem to facilitate HART communication.
The Flow-X flow computer uses an internal 250 Ω resistor for its analog inputs, which is adequate for HART communication.
The flow computer supports both a single HART transmitter and multiple HART transmitter per loop.
If of a single HART device in the loop, the 4-20 mA signal is measured in parallel and available in the
software.
In systems with HART inputs where a separate external analog input common is used, it is required
to connect the analog input common and the 0 V with a 50 μF capacitor in-between.
Popular Articles
How to connect prover signals
CONNECT PROVER SIGNALS In this HowTo will be explained how prover signals should be connected. This depends on the Flow-X type and the prover setup. Flow-X/P Ball prover / Compact prover. Connect the flow pulse signals to the corresponding modules ...
How to print a snapshot report on startup in Flow-X
PRINT A SNAPSHOT REPORT ON STARTUP IN FLOW-X This document describes how to generate a snapshot repot whenever the Flow-X flow computer starts up for any reason. Define a new Calculation group Define a new tag to latch the latest startup time Give ...
Adding new users to the FlowX
Security Files In Flow-Xpress users and passwords can be modified and added both in online mode (directly in the flow computer, also for multiple flow computers at once) and offline mode (in the loaded application file). Each user has a specific ...
USE MODBUS SLAVE WHILE READING VALUES FROM A DEVICE
When using the Modbus Slave protocol, a synchronization problem may occur while reading values from a device. This HowTo explains how to overcome this problem.
SET UP FLOW COMPUTERS IN COMBINATION WITH A PROLINX DEVICE
This How To explains how you can set up one or more flow computers when a ProLinx device for HART master is also present. The flow computer’s HART master protocol is acting such that the flow computer is either listening or an active sender. When two ...
Related Articles
Flow-X Ground Wiring
Ground wiring The Flow-X flow computer uses the following separate ground connections: one common ground for the power supply and the digital signals ('0 V') one isolated common ground for the analog inputs ('Analog input common') one isolated common ...
Flow-X Analog output calibration
The procedure to calibrate an analog output is based on a 4-20 mA meter. 1. Connect the mA meter in series with the load. 2. Go to the analog output calibration display. Display → Diagnostics, IO, <Module x>, Calibration, Analog outputs With x the ...
How to simulate proving using a FlowX flow computer
How to simulate proving with the Flow-X flow computer This How to instruction will provide an example of how to program the FlowX to simulate proving a meter. Most newer flow computers require live pulses and detector inputs to prove a meter. Wiring ...
How to print a snapshot report on startup in Flow-X
PRINT A SNAPSHOT REPORT ON STARTUP IN FLOW-X This document describes how to generate a snapshot repot whenever the Flow-X flow computer starts up for any reason. Define a new Calculation group Define a new tag to latch the latest startup time Give ...
SET UP FLOW COMPUTERS IN COMBINATION WITH A PROLINX DEVICE
This How To explains how you can set up one or more flow computers when a ProLinx device for HART master is also present. The flow computer’s HART master protocol is acting such that the flow computer is either listening or an active sender. When two ...